Version 2.0
Replacement
Standardised measure
EFFEL programme

Replacement of Air Conditioning Units up to 12 kW in Non-Residential Spaces

Refrigeration Technology

Measure Goal

The goal is to standardize the calculation of electricity savings that are triggered by replacing inefficient room air conditioning units up to 12 kW in non-residential rooms with energy-efficient units.

Examples and Scenarios

5.0 Rp./kWh
0.1 Rp./kWh10.0 Rp./kWh
Scenario A
Savings

Replacement of 10 room air conditioning units with 5 kW cooling capacity each

45'000
kWh

eligible kWh, accumulated over the measure's lifetime

Funding contribution
CHF 2’250

Inputs

Kälteleistung: 5 kW, EER vorher: 2.5, EER nachher: 3.5, Volllaststunden: 1'200 h/a

Requirements

Only measures that meet the requirements of the Energy Ordinance (SR 730.01; EnV) can be credited. The additional requirements for the technical characteristics and for the implementation of the measure are set out in Table 1.

Old systemNew system
TechnologyMains-operated split or multi-split air conditioners with a rated cooling capacity Prated of up to 12 kW that fall within the scope of Annex 1.13 of the Energy Efficiency Ordinance (SR 730.02; EnEV) are covered by this measure.
Energy efficiency-Energy efficiency class (cooling) of at least A+++
Installation locationThe cooled area of the building/rooms without residential use must be 150 m² or smaller and must be determined in accordance with SIA 380:2015. The building's altitude must not exceed 800 metres above sea level.
SizingThe total installed rated cooling capacity of the new system must be less than or equal to the total installed rated cooling capacity of the old system.
ImplementationThe replacement and commissioning of the new system must be carried out by a qualified specialist or company.
DisposalThe consumption-relevant components of the old devices may not continue to be operated within Switzerland. Proper disposal or export must be demonstrable on request.

Proof of compliance

Compliance with the requirements must be demonstrated by the following documents. The documents listed in Table 2 are an integral part of the proof of measure implementation.

  • 1.Explanation (PDF format, max. 2 A4 pages) of how it is ensured that the replaced devices were properly disposed of (e.g. by means of declarations, disposal items on contractor invoices, etc.).
  • 2.Invoice documents (PDF, PNG or JPEG format)

Would you like to submit your project or need help?

Contact

Symbols, Terms and Units

SymbolDescriptionUnit
ΔEannual electricity savingskWh/a
ΔEecocumulative electricity savingskWh
PKcooling capacitykW
EEREnergy Efficiency Ratio—
hVLannual full load hoursh/a
Nsstandard effective durationa

Calculation Formulas

Annual Electricity Savings

ΔE = PK × hVL × (1/EERvor - 1/EERnach)

The annual electricity savings result from the cooling capacity, full load hours and the difference in efficiency before and after replacement.

Cumulative Electricity Savings

ΔEeco = ΔE × Ns

The cumulative electricity savings result from the annual savings multiplied by the standard effective duration.

Downloads

Documentation (PDF)
Complete technical documentation including calculation basis
Download DOC
Excel Calculator (XLSX)
Interactive calculation tool for savings
Download PRO

Part of the EFFEL programme

Standardised measures are one of two measure types in the EFFEL programme (efficiency improvements by electricity suppliers, Art. 46b EnG). They follow a predefined SFOE catalogue with fixed savings values.

More about the EFFEL programme