Version 2.0
Operational Optimization
Standardised measure
EFFEL programme

Optimization of Existing Indoor Lighting Systems

Lighting

Measure Goal

The goal is to standardize the calculation of electricity savings triggered by the optimization of existing indoor lighting systems, particularly through the installation or retrofitting of presence and daylight controls, taking into account all consumption-relevant parameters.

Requirements

Only measures that meet the requirements of the Energy Ordinance (SR 730.01; EnV) can be credited. The additional requirements for the technical characteristics and for the implementation of the measure are set out in Table 1.

Old systemNew system
Quality verification-Minergie limit value according to SIA 387/4:2023 Illuminance no more than 20% above the minimum values according to SN EN 12464-1
ImplementationPlanning, installation and commissioning of the new system must be carried out by a qualified specialist / company and metrologically verified after completion.
DisposalThe consumption-relevant components of the old devices may not continue to be operated within Switzerland. Proper disposal or export must be demonstrable on request.

Proof of compliance

Compliance with the requirements must be demonstrated by the following documents. The documents listed in Table 2 are an integral part of the proof of measure implementation.

  • 1.Invoice documents (PDF, PNG or JPEG format)
  • 2.Explanation (PDF format, max. 2 A4 pages) of how it is ensured that the replaced devices were properly disposed of (e.g. by means of declarations, disposal items on contractor invoices, etc.).
  • 3.A metrological report (PDF format) documenting the correct illuminance levels after commissioning
  • 4.An energy verification according to SIA 387/4:2023. Permitted tools for this are:

Permitted tools

  • SFOE Excel tool (SIA 387/4) — A free Excel tool for calculating the energy demand according to SIA standard 387/4.
  • ReluxEnergy CH — A paid calculation and verification tool for lighting installations according to SIA standard 387/4.
  • LightTool.ch — A free online tool for calculating the energy demand according to SIA standard 387/4

Would you like to submit your project or need help?

Contact

Symbols, Terms and Units

SymbolDescriptionUnit
Eannual electricity consumptionkWh/a
ΔEecocumulative electricity savingskWh
fPpresence factor-
fTLdaylight factor-
Nsstandard effective durationa

Calculation Formulas

Electricity Savings through Presence Control

ΔEP = Ewithout × (1 - fP)

The electricity savings through presence control result from electricity consumption without control multiplied by the savings potential of the presence factor.

Electricity Savings through Daylight Control

ΔETL = Ewithout × (1 - fTL)

The electricity savings through daylight control result from electricity consumption without control multiplied by the savings potential of the daylight factor.

Combined Control

ΔE = Ewithout × (1 - fP × fTL)

With combined presence and daylight control, both factors are considered multiplicatively.

Cumulative Electricity Savings

ΔEeco = ΔE × Ns × f

The cumulative electricity savings result from the annual savings multiplied by the standard effective duration and the correction factor.

Downloads